საკონტროლო პანელი |
J408-4
Conventional Control Panels
|
|
|
Product description: |
4 zone fire control panel |
4controlled, balanced, bypassable input zones |
Power supply: 230 Vac 10% RS485 bus |
27.6 Vdc 1.5 A switching supply/battery-charger |
Compartment for two 12 V 7 Ah batteries Dimensions (wxhxd): 354x280x100 mm Weight (without batteries): max. 4,5 Kg |
|
|
|
|
|
|
|
FeaturesConforms with EN54
Up to to 21 devices can be connected to each zone: conventional fire
detectors, alarm buttons, gas detectors
Gas zone compatible with 4 20 mA gas detectors
One alarm-repeat output (open collector) for each input zone
Manual call point recognition
Signals missing detectors
2 supervised, silenceable, bypassable 24 V alarm output for the activation
of piezoelectric sirens, fire bells and flashers
Silenceable fault-warning output for the activation of
signalling and dsauxiliary devices
Supervised fire output for telephone dialler activation
Programmable open-collector output
Dry contact alarm-relay for the activation of auxiliary devices
Day/Night mode
Alarm verification time
Programmable restoral and reset times
Programmable from PC or keypad
50 event log viewed via PC
Alarm/fault memory activated until next reset
Command for silencing sirens
Keypad commands require key or pin code
|
|
J408-8
Conventional Control Panels
|
|
|
Product description: |
8 zone fire control panel |
8 controlled, balanced, bypassable input zones |
Power supply: 230 Vac 10% RS485 bus |
27.6 Vdc 1.5 A switching supply/battery-charger |
Compartment for two 12 V 7 Ah batteries |
Dimensions (wxhxd): 354x280x100 mm |
Weight (without batteries): max. 4,5 Kg |
|
|
|
|
FeaturesConforms with EN54
Up to to 21 devices can be connected to each zone: conventional fire
detectors, alarm buttons, gas detectors
Gas zone compatible with 4 20 mA gas detectors
One alarm-repeat output (open collector) for each input zone
Manual call point recognition
Signals missing detectors
2 supervised, silenceable, bypassable 24 V alarm output for the activation
of piezoelectric sirens, fire bells and flashers
Silenceable fault-warning output for the activation of
signalling and dsauxiliary devices
Supervised fire output for telephone dialler activation
Programmable open-collector output
Dry contact alarm-relay for the activation of auxiliary devices
Day/Night mode
Alarm verification time
Programmable restoral and reset times
Programmable from PC or keypad
50 event log viewed via PC
Alarm/fault memory activated until next reset
Command for silencing sirens
Keypad commands require key or pin code
|
J424
Conventional Control Panels
|
|
|
Product description: |
Expandable fire control panel. |
8 controlled, balanced, bypassable input zones expandable to 24 by means of two 8 zone expanders Optional backlit display RS485 bus |
Power supply: 230 Vac 10% 27.6 Vdc 2.5 A switching supply/battery-charger |
Compartment for two 12 Vdc 17 Ah batteries Dimensions (wxhxd): 422x502x116 mm Weight (without batteries): max. 8.5 Kg |
|
|
|
|
|
|
|
|
Conforms with EN54
Up to 21 devices can be connected to each zone: conventional fire
detectors, alarm buttons, gas detectors
Gas zone compatible with 4 20 mA gas detectors
One alarm-repeat output (open collector) for each input zone
Manual call point recognition
Signals missing detectors
2 supervised, silenceable, bypassable 24 V alarm output
for the activation of piezoelectric sirens, fire bells and flashers
Silenceable fault-warning output for the activation of signalling
and auxiliary devices
Supervised fire output for telephone dialler activation
Programmable open-collector output
Dry contact alarm-relay for the activation of auxiliary devices
Day/Night mode
Alarm verification time
Programmable restoral and reset times
Programmable from PC or keypad
50 event log viewed via PC
Alarm/fault memory activated until next reset
Command for silencing sirens
Keypad commands require key or pin code
|
|
J400-EXT
|
|
|
Product description: |
Extinguisher module with microprocessor control
Output for electro-valves controlled by logic (AND/OR) between the status of the control panel zones
Programmable extinguishment delay
Output signals: extinguishment delay, extinguishment and released
Input for the forced activation of the extinguishment devices - Input for the pressure switch
Fault signalling on pressure-switch supply line
Fault signalling on input lines
Bypass of extinguishment devices in the event of false alarm
Inputs for selecting manual or automatic mode,
extinguishment inhibit and power supply supervision |
|
|
|
|
|
|
|
|
|
|
|
J400-LCD
|
|
|
Product description: |
Display module |
Backlit LCD display module, two lines with 16
characters per line. |
Main text regarding the systems status and it is |
equipped with 6 scroll keys. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
J400EXP8
|
|
|
Product description: |
8 zones expander module for J424 panels |
(8 balanced, bypassable fire zones) |
|
|
|
|
|
|
|
|
|
|
|
|